Enertech Global 
EAV - EME/EMD Rev. A Models
Installaon and Operaons Manual

Check that the pipe system is complete.
Check the pipe system for leaks.
Check that the electrical installaon is prepared.
Check that the electrical supply is connected so that the
compressor crankcase heater can start warming up the
compressor, if necessary.
The compressor crankcase heater must have been acve
for at least 3 hours before compressor operaon can be
iniated. This is done by connecng control voltage. EAV
permits compressor start aer the compressor has been
warmed up. This can take up to 3 hours.

1. Fill the hydronic system to the necessary pressure.
2. Vent the system using the venng port on the ex tube
(included) and possibly the circulaon pump.
3. See indoor secon installaon for detailed ushing/purging
piping system of air.

1. Communicaon cable, terminal block (X22:1-4) must be
connected.
2. Turn the isolator switch on.
3. Ensure that the EAV is connected to the power source.
4. Reinstall the removed panels and cover.
5. Aer the power to EAV has been switched on and there
is a compressor demand from the indoor module/control
module, the compressor starts once it has warmed up, aer
max 180 minutes. The length of this me delay depends on
whether the compressor has been warmed up previously.
See chapter Preparaons secon, above.
6. Adjust menu sengs via the indoor HMI (touchscreen
Human Machine Interface) as necessary.
7. Fill in the commissioning report.
8. Remove the protecve lm from the cover on EAV.

Air is inially released from the water/anfreeze soluon and
venng may be necessary. If bubbling sounds can be heard from
the heat pump, the circulaon pump and piping/fan coils the
enre system will require further ushing/purging. When the
system is stable (correct pressure and all air eliminated) the
control system can be set as required.

EAV is equipped with an internal electronic controller that
handles all funcons necessary for operaon of the heat pump,
e.g. defrost cycle, stop at max/min. temperature, connecon
of the compressor heater, and protecve funcons during
operaon. Temperatures, number of starts and run me, are
displayed in the indoor module/control module.
The integrated control shows informaon via status-LEDs and
can be used during servicing.
Under normal operang condions the home owner does not
need to have access to the controller.
EAV communicates with the Enertech indoor module/control
module, which means that all sengs and measurement values
from EAV are adjusted and displayed on the indoor module/
control module.
