Enertech Global 
EAV - EME/EMD Rev. A Models
Installaon and Operaons Manual
Potential ProblemChemical(s)orCondition RangeforStainlessSteelBPHE
Calcium&Magnesium Lessthan0.1ppm
pHRange 7.59
TotalDissolvedSolids Norigidsetpoint
Ammonia,AmmoniumHydroxide
Not allowed
AmmoniumChloride,Ammonium Lessthan220ppm
CalciumChloride/Sodium Notallowed
Chlorine Notallowed
HydrogenSulfide Lessthan0.05ppm
Sulfates Lessthan100ppm
HydrogenCarbonate Between60ppmand200ppm
HydrogenCarbonate/Sulfates Morethan1.5ppm
Calcium&Magnesium/HydrogenCarbonate Morethan0.5ppm
Conductivity Lessthan500micros/cm
IronBacteria Notallowed
IronOxide Lessthan0.2ppm
SuspendedSolids 40meshstrainerrequired
WaterVelocity Lessthan5.5m/sintheport
Scaling
Corrosion
Biological
Erosion
Notes:
1. Hardnessinppmisequivalenttohardnessinmg/l.
2. Grains/gallon=ppmdividedby17.1.
3. Unitinternalheatexchangersarenotrecommendedforpoolapplicationsorwateroutsidetherangeof
thetable.Secondaryheatexchangersarerequiredforpoolorotherapplicationsnotmeetingthe
requirementsshownabove.
4. Saltwaterapplications(approx.25,000ppm)requiresecondaryheatexchangersduetocopperpiping
betweentheheatexchanger.
5. Filterformaximumof600micronsize.



1. Hardness in ppm is equivalent to hardness in mg/l.
2. Grains/ gallon = ppm divided by 17.1.
3. Unit internal heat exchangers are not recommended for pool applicaons or water outside the range of the table. Secondary
heat exchangers are required for pool or other applicaons not meeng the requirements shown above.
4. Saltwater applicaons (approx. 25,000 ppm) require secondary heat exchangers due to copper piping between the heat
exchanger.
5. Filter for maximum of 600 micron size.
