Enertech Global
EAV - EME/EMD Rev. A Models
Installaon and Operaons Manual
The OAT terminals in the EME/EMD indoor module are not used.
The out door sensor is installed and wired in the Outdoor Unit,
Sensor BT28.
Outdoor reset control will vary the design load temperature
based on outdoor temperature. The colder the outside
temperature, the warmer the load water/anfreeze soluon
temperature. This oers several advantages. The COP of the
system is improved by targeng the lowest outlet temperatures
possible. Addionally, user comfort is improved by maintaining
ideal temperatures for the current outdoor condions. If
necessary, the EAV can operate without outdoor reset by seng
a stac load water/anfreeze soluon temperature (see Secon
9).
The outdoor temperature is a running one hour average
to avoid dramac shis.
The EAV ulizes a set of temperature curves as seen in Figure
21. The default curve is #3 and has been found to work in
many installaons. Depending on the load calculaon and
environmental requirements, a dierent curve may be
preferable: The higher numbered curves produce higher radiant
oor temperatures for a given outdoor temperature while
the lower numbered curves produce lower temperatures. For
example, at 30°F outdoor temperature, curve #3 will produce
79°F outlet temperature. Changing to curve #4 would produce
84°F outlet at that same condion.
1
2
3
4
5
6
7
8
9
10
11
1213
14
15
59
69
79
89
99
109
119
129
139
-30-1010305070
Supply Temeprature °F
Outdoor Temperature °F
Heang Curves
⚠⚠
Floors occupied in areas 85
Floors in perimeter areas 95
Floors in bathrooms 91
Floors in hallways, secondary
rooms
95