EasyManua.ls Logo

Enertech EAV060 - Load Piping Installation

Default Icon
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Enertech Global 
EAV - EME/EMD Rev. A Models
Installaon and Operaons Manual

It is important that the load side piping of the EAV system is
sized properly for the required ow rates and is ushed and
lled with good quality water and treatment. This will help
ensure that the longevity of the pump(s), braze plates, and other
load side components. 


The Wye Strainer, which contains a #40 mesh, will collect debris
le in the piping aer the system has been ushed and lled.
Per the installaon diagrams shown in
boiler drains and isolaon valves need to be integrated into the
load piping for proper ushing of the system at start up, as well
as for future service. Full port isolaon valves should be used in
order to ensure low pressure drop throughout the system.
Generally, the recommended load side piping arrangement
is designed as a parallel direct return system. Each zone is in
parallel and returns directly to the heat pump. Zone valves
should be ulized on each circuit to control the soluon ow
to each manifold/zone/circuit or distribuon device. Enertech
recommends zone valves have a CV rang of 8.9 or higher to
help guarantee proper ow and low pressure drop throughout
the system. All zone valves must be on/o style valves. If it is
determined that any of the zone’s ow rates are less than 5
GPM, a pressure dierenal bypass valve is required for proper
unit operaon (Enertech P/N: ADBV4A).
CAUTION
THIS SYSTEM UTILIZES A PRESSURIZED LOAD CIRCUIT. PLEASE ENSURE THE FOLLOWING:
1. The load side piping is flushed completely and purged of air (see Secon 6, Figures 7a to 7j).
2. The differenal bypass valve is installed, and in the correct orientaon (see page 16 and
drawing below).
3. The minimum pump speed is set to allow 5 GPM through the bypass valve
with all zones closed (see page 16) if hydraulic separator or buffer tank is not
used (a hydraulic separator or buffer tank is recommended).
NOTICE: A flush cart is required for purging air from the load side piping. See WV I.O.M.,
Figures 6a to 6c for valve arrangement and Secon 6 (Flushing and Filling) for flushing steps.
Remove this page from the manual before providing to building owner.
3. The minimum pump speed is set to allow 5 GPM through the bypass valve
with all zones closed (see page 16) if hydraulic separator or buffer tank is not
used (a hydraulic separator or buffer tank is recommended).
Referencefor installaon of a bypass valve.
Follow the steps below for valve sengs.
1. The bypass valve seng should be adjusted during the
Startup Wizard in  when seng the minimum
pump speed (manual mode).
2. Set the adjustment indicator at 4.5 on the bypass valve.
3. In the Startup Wizard, start with the default minimum pump
speed at 60%. Open the zone valve for the smallest zone
(lowest ow rate). It will be important to know the design
ow rate for the smallest zone. For example, if the smallest
zone has 5 - 1/2” PEX circuits, the design ow rate is
typically 2.5 to 4 GPM. The combinaon of the minimum
pump speed and the bypass should provide a minimum for
5 GPM.
4. Turn the adjustment indicator counter-clockwise to allow
the combined ow of the smallest zone and the bypass
valve to equal 5 GPM. The minimum pump speed may need
to be adjusted to higher than 60%, depending upon the size
of the zone.

An automac air eliminaon device and expansion tank are
factory installed in the indoor unit. They help remove any micro-
bubbles sll remaining aer purging and lling. The expansion
tank maintains minimum pressure in the hydronic system for
proper pump operaon.
Most local codes require certain components be installed within
the system. Local codes should be followed when determining
the exact requirements. A pressure relief valve may be required,
which should be rated for 30 PSI and terminated 6” from the
oor surface. Addionally, back-ow preventer may be required
and should be installed if a make-up water line is connected
from the water source to the load side piping of the system.
 Even if a back-ow preventer is not required, it is highly
recommended.






All interior piping must be sized for proper ow rates and
pressure loss. Insulaon should be used on all inside piping
when minimum temperatures are expected to be below the dew
point (less than approximately 50°F). All pipe insulaon should
be made of closed cell and have a minimum wall thickness
of 3/8” for interior piping. Piping between the Outdoor Unit
and the Indoor Module should be at least 3/4” wall thickness.
All piping insulaon should be glued and sealed to prevent
condensaon and dripping. Interior piping may consist of the
following materials: PEX, copper, or stainless steel hose (hose kit
only). PVC and other piping types are not recommended.


Table of Contents

Related product manuals