EAV - EME/EMD Rev. A Models
Installaon and Operaons Manual

The system should be inspected before it is commissioned. The inspecon must be carried out by a suitably qualied person. Fill
in the page for informaon about installaon data in the User manual.
   

System Flushed with Flush Cart
System Purged of Air
Anfreeze type and %
Flow Rate Veried

Disconnects (indoor/outdoor)
Installed
Breaker and Wire Sizes Veried
Immersion Heaters Wired
Communicaon Cable Connected
EAV Addressed (only when cascade
connecon)
High Voltage Measurement (Outdoor)
High Voltage Measurement (Indoor)
Transformer Tap (208V or 240V)
Veried

Condensate Drain
Insulaon Condensate Drain,
Thickness
 Check the connecons, main voltage and low voltage before the machine is started, to prevent damage to the heat pump
electronics.
