PLATINOUS SERIES CONTROLLER MANUAL
64
The setting values for these parameters will vary depending upon the chamber capacity
and the product being tested. The following table gives some approximate “base” or
“starting” values for these parameters based on the desired change rate. These values
are intended to be used as a reference and the user may find that product temperature
control may work slightly better using different numeric values.
Table 5.8. Product Temperature Control Tuning Parameters Reference Table
Change Rate
(°C/min)
P Filter (I) D
0-1 1.0 36.0 2.0
1-3 1.1 40.0 2.2
3-5 1.3 47.0 2.6
5-7 1.5 54.0 3.0
7-10 1.7 61.0 3.4
10+ 2.0 72.0 4.0
5.11.12. Service
This mode is reserved for serviceman use and cannot be accessed or used by the user.
Tampering with parameters can lead to trouble.
ESPEC will not assume responsibility for equipment trouble whatsoever when resulting
from unauthorized use of the service mode.