MT100 Multipoint Flow Meter INSTALLATION
I/O Connections
As shown in Figure 23 the SB4 main board provides an input/output signal interface for connection to various peripheral interfaces. For
these interfaces, route the cable/wires through a conduit opening at the enclosure bottom and connect to the appropriate
connector/terminals.
HART
Connect the installation HART wiring to the appropriate J9 Phoenix connector terminals depending on the application. The connector
accepts 28-16 AWG (0.14 mm
2
-1.5 mm
2
) wire (refer to Table 2, page 23 for wire size vs. length info).
Single Connection The instrument supplies power to the loop and controls the current as well. For this application connect HART+
to J9-1 (INT+) and HART- to J9-2 (INT-).
Network (Multidrop) Connection The instrument receives loop power from the network, and controls the current. For this
application connect external HART+ to J9-2 (EXT+) and external HART- to J9-4 (RTN).
The block diagram in Figure 24 below shows the single connection and multidrop HART setups. Use a 250 Ω 1%, 0.3 W resistor as shown in the
diagram below only if the external HART interface/wiring does not have this resistance built-in (HART requires a minimum loop resistance of 230 Ω).
C
ABLING RECOMMENDATION
Use a shielded, twisted-pair instrument grade wire (min. 24 AWG for runs less than 5000 ft/1500 m; min. 20 AWG for longer distances). The RC
value of the wire (Total Resistance x Total Capacitance) must be less than 65 µs (not a concern for point-to-point topology with a run less than
328 ft/100 m). A cable designed for HART/RS-485 such as Belden 3105A is recommended for complex setups and/or particularly long runs.
Note:
The HART communications digital signals are superimposed on top of the channel #1 current loop (4-20 mA) output.
When HART communications is in use, the HART current loop channel #1 MUST be configured as FLOW to comply
with the HART protocol. The channel #1 current loop output is configured as FLOW by default at the factory.
MT100
HART
J9-1
J9-2
Internal Loop Power External Loop Power
HART
I/O
HART
HART HART+
+
I/O
HART
Master
R
LOAD
J9-1
NC
MT100
HART
Master
R
LOAD
Network P.S.
24 VDC
HART
+
J9-2
J9-4
(a) HART Single Connection
MT100
HART
J9-1
J9-4
J9-2
MT100
HART
J9-1
J9-4
J9-2
MT100
HART
J9-1
J9-4
J9-2
MT100
HART
Network P.S.
24 VDC
HART
Master
J9-1
R
LOAD
HART
I/O
J9-4
J9-2
HART+ HART
(b) HART Network, Multidrop
C01364-1-1
Figure 24 Single Connection and Multidrop HART Setups