MT100 Multipoint Flow Meter OPERATION
HART Command List Reference
The HART commands are divided into three classes.
● Universal Commands
● Common Practice Commands
● Device Specific Commands
Barring no communication error, a field or slave device returns a response code as part of the 2-byte status response to a command. Refer
to Command Status Bytes on page 69. The MT100 response codes listed in the following command summaries are a subset of the
response codes listed in the HART specification.
MT100 HART Universal Commands
The MT100 HART supports Universal Commands 0 through 22 and 38 and 48. Commands 4 and 5 are reserved under Universal
Command Specification Rev. 7.1 (HCF_SPEC-127, Revision 7.1) and not implemented in this specification. There is no HART command
10. Table 7 below summarizes the instrument’s HART Universal command set and the data associated with each command.
Table 7 – HART Universal Commands
Command 0: Read Unique Identifier
Minimum number of preambles from master to slave
HART Protocol Revision Number: 7
Device Revision Number: 1
Software Revision Number: 1
(Most Significant 5 Bits) Hardware Revision Level: 1
Physical Signaling Code: 00 = Bell 202 Current (4-20 mA)
Minimum number of preambles from the slave to master
Maximum Number of Device Variables
Configuration Change Counter
Extended Field Device Status
Manufacturer ID Code: 166
DEC
/00A6
HEX
(FCI)
Private Label Distributor Code
Device Profile = 1 “HART Process Automation Device”
No Command-Specific Errors
Fluid Components International LLC 47