INSTALLATION MT100 Multipoint Flow Meter
Source/Sink Outputs
Wire the source/sink outputs via the J8 Phoenix connector terminals as required for your device (using sink and/or source output as
appropriate) as shown in Figure 27 and Figure 28 below. The connector accepts 28-16 AWG (0.14 mm
2
-1.5 mm
2
) wire. The source/sink
outputs provide a pulse (frequency) output. Observe the output power limits listed below.
Sink Output: 40 VDC maximum, 150 mA maximum (external, user-supplied power source)
Source Output: 22 ±2 VDC output, 25 mA maximum (supplied by the flow meter)
Figure 27 Sink Output
(Typical)
External 24-40 VDC
Power Supply
150 mA max.
External Device
(Counter, etc.)
COM
SINK
USER WIRING
J8
FLOW METER SIDE USER SIDE
2
3
C01402-1-1
CURRENT FLOW
+
J8
(Typical)
External
Device
(Counter, etc.)
24 VDC
25 mA max.
GND
USER WIRING
FLOW METER SIDE USER SIDE
SOURCE
Alternate wiring,
see note below.
Note: Use voltage divider resistor
network if flow meter source voltage
(24 VDC) exceeds your device input.
1
2
C01403-1-1
CURRENT FLOW
Figure 28 Source Output