EasyManua.ls Logo

Flexim FLUXUS F801 - E System Design in Accordance with IBExU07 ATEX1061

Default Icon
160 pages
Print Icon
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FLUXUS ADM 8027, F801, ADM 8127B E System Design in Accordance with IBExU07ATEX1061
160 UMFLUXUS_F8V4-6-1EN, 2018-10-10
E System Design in Accordance with IBExU07ATEX1061
cables
L-YY(ZG)Y-2x2x0.5-60V-blue:
operating capacitance: max. 90 nF/km
inductance (loop 800 Hz): max. 0.8 mH/km
length: max. 80 m
power supply unit
NG3-12ib
FHF Bergbautechnik
U
0
= 12.15 V
I
0
= 1.27 A
C
ext
= 15 μF (at L
0
= 0 H)
L
ext
= 70 μH (at C
0
= 0 F)
-20 °C T
a
+60 °C
transmitter
FLUXUS ADM 8127B
FLEXIM GmbH
U
i
13.2 V DC
L
i
, C
i
negligible
-20 °C T
a
+50 °C
terminal
+
-
L-
L+
PE
or
L-2YYC(ZG)Y-2x2x0.5:
operating capacitance: max. 55 nF/km
inductance (loop 800 Hz): max. 0.8 mH/km
length: max. 80 m
part contained in system approval IBExU07ATEX1061
frequency output 5…15 Hz
binary output
(not part of this system approval
because completely galvanically isolated)
transducer circuits
not intrinsically
safe
230 V AC
terminal

Table of Contents