2.1.2 Installing Power Distribution Unit (2U)
This section explains how to install a 2U power distribution unit (12 outlet type or 16 outlet type) in a rack.
This section explains how to install a 12 outlet type power distribution unit as an example. This installa-
tion method can also be applied to a 16 outlet type power distribution unit.
1 Attach the M5 cage nuts to the rear rack pillar.
Attachment positions
On either side, insert eight M5 cage nuts in the 1st, 3rd, 4th, and 6th holes above the power distribu-
tion unit base line.
1U
1U
2U
Power distribution unit
Power distribution unit
(Rack pillar: rear)
Power distribution unit
base line
M5 cage nut M5 cage nut
1st hole
3rd hole
4th hole
6th hole
1st hole
3rd hole
4th hole
6th hole
[Left] [Right]
Attachment procedure
Clip the M5 cage nut tabs into the desired hole from the inside.
Side view
M5 cage nut
Rack pillar (square hole)
Chapter 2 Rack Installation
2.1 Power Distribution Unit Installation (for Regions other than the EMEIA, Central American, and Caribbean Regions)
26
FUJITSU Storage ETERNUS AF250 S2, ETERNUS AF250 All-Flash Arrays
Configuration Guide (Basic)
Copyright 2017 FUJITSU LIMITED
P3AG-1832-04ENZ0