Powering Off
This section explains how to turn off the ETERNUS DX.
To turn off the ETERNUS DX, perform one of the procedures below.
• Via the power switch
Press the Power switch to turn off the
ETERNUS DX.
• Via ETERNUS Web GUI or ETERNUS CLI
Use ETERNUS Web GUI or ETERNUS CLI to turn off the ETERNUS DX.
The following methods can be used to turn off the power by linking with the server.
• Via the power synchronized unit
Use the power synchronized unit to turn off the ETERNUS DX.
IMPORTANT
• When the ETERNUS DX is turned off, the power shuts off after the data in the cache memory is written to
the drives. As a result, it may take the following time for the power supply to be completely turned off.
Table 2 Time Required to Turn the Power Off
Model
Deduplication/
Compression function
is disabled
Deduplication/
Compression function
is enabled
Unified configuration (*1)
VLAN/Bonding maximum
configuration
DX60 S5 Approx. 8 minutes
(max. 10 minutes)
— — —
DX100 S5 Approx. 8 minutes
(max. 10 minutes)
— Approx. 13 minutes (max.
25 minutes)
Approx. 20 minutes (max.
25 minutes)
DX200 S5 Approx. 8 minutes
(max. 10 minutes)
Approx. 12 minutes
(max. 14 minutes)
Approx. 13 minutes (max.
25 minutes)
Approx. 20 minutes (max.
25 minutes)
DX500 S5 Approx. 10 minutes
(max. 15 minutes)
Approx. 18 minutes
(max. 23 minutes)
Approx. 15 minutes (max.
25 minutes)
Approx. 20 minutes (max.
25 minutes)
DX600 S5 Approx. 10 minutes
(max. 15 minutes)
Approx. 19 minutes
(max. 24 minutes)
Approx. 15 minutes (max.
25 minutes)
Approx. 20 minutes (max.
25 minutes)
DX900 S5
(*2)
Approx. 10 minutes
(max. 20 minutes)
Approx. 11 minutes
(max. 21 minutes)
— —
*1: The time required to turn the power on for the Unified configuration depends on the NAS configuration (or the number of
shared folders and the number of VLAN/Bonding configurations).
*2: The ETERNUS DX900 S5 supports the Compression function only.
• Do not turn off the power of the ETERNUS DX and the network devices that connect the ETERNUS DX to a
server while the server is operating. This may result in the loss of data or prevent data from being saved
in the ETERNUS DX.
• When using a power synchronized unit for power control, turn off the power of the
ETERNUS DX via the
power synchronized unit. When a power synchronized unit is connected, the power of the ETERNUS DX is
automatically turned on because the power synchronization function is activated.
• If the REMOTE LED on the ETERNUS DX500 S5/DX600 S5 is green, turn off the ETERNUS DX500 S5/DX600
S5 by linking with the server. Pressing the Power switch does not turn off the ETERNUS DX500 S5/DX600
S5.
• To turn off the ETERNUS DX, use the Power switch, a power synchronized unit, ETERNUS Web GUI, or
ETERNUS CLI. If any other method is used to turn off the ETERNUS DX, the replacement cycle for the
battery is shortened significantly because the battery continues to charge and discharge.