EasyManua.ls Logo

FULTON Vantage VTG 2000 - Network Parameter Configuration and Address Listings

FULTON Vantage VTG 2000
149 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Questions? Call (315) 298-8510, or visit us online at www.fulton.com
40
This manual is provided as a guide
to the correct operation and
maintenance of your equipment,
and should be read in its entirety
and be made permanently
available to the staff responsible
for equipment operation. It should
not, however be considered as a
complete code of practice, nor
should it replace existing codes or
standards which may be
applicable. Synex reserves the
right to change any part of this
installation, operation and
maintenance manual without
notice.
Do not install, operate, service, or
repair any component of this
equipment unless you are qualified
and fully understand all
requirements and procedures.
All information in this manual is for
reference and guidance purposes,
and does not substitute for
required professional training,
conduct, and strict adherence to
applicable jurisdictional
/professional codes or regulations.
Network Parameter Configuration and
Address Listings
The ModSync Sequencing System provides a Modbus interface to communicate the
status of each condensing boiler in the hydronic heating loop to a Building
Management System. This network can also be used to receive a system
enable/disable and remote setpoint commands from the Building Management
System. BACnet and LonWorks options are also available.
The following table details the communication parameters and the ModSync
addresses available for the ModSync.
*Please contact Synex Controls to request a points list mapped for your equipment.