SECTION 2 VTG-IOM-2016-1214 INSTALLATION
Install pH Neutralization Kit
The pH Neutralization Kit uses a consumable medium to bring the pH level of the
boiler’s condensate to a neutral level. It is not a replacement or alternative for the
Condensate Drain Trap. See Figures 6 and 10.
Adhere to the following for installation:
1. Use stainless or galvanized pipe and ttings to connect condensate drain
to kit.
2. Connect kit downstream of Condensate Drain Trap. See Figure 10.
3. Pipe outlet to appropriate drain. It is acceptable to use PVC or CPVC on the
outlet to drain.
4. Check condensate pH periodically.
NOTE: Replacement bags are available from your Fulton Representative. The
medium in the container will neutralize the condensate of 12 MM Btu’s for
approximately 6 months (Fulton Part No. 2-30-0015800).
Install #2 Fuel Oil Piping
FIGURE 11 OIL PUMP LOCATION VTG2000DF TO VTG6000DF
#2 Fuel Oil Piping (For Dual Fuel Gas/Oil Burner)
Adhere to the following for Vantage boilers with the dual fuel gas/oil Burner (see
Figure 11):
1. The Vantage dual fuel boiler is suitable for ring light distillate fuel oil
conforming to ASTM D396 only, commonly known as #2 fuel oil. DO NOT
USE JP-8, GASOLINE, CRANKCASE OIL OR ANY OIL CONTAINING GASOLINE.
If in doubt, contact your Fulton representative prior to operation.
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
The minimum return water
temperature to the boiler is 140 F
(60 C) when ring on standard #2 fuel
oil. Failure to maintain this will void
the warranty.