EasyManua.ls Logo

FULTON Vantage VTG 2000 - Operating Temperatures and Fuel Selection

FULTON Vantage VTG 2000
149 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© The Fulton Companies 2016
3-16
OPERATION VTG-IOM-2016-1214 SECTION 3
Operating Temperatures and Fuel Selection
Use Table 9 to determine minimum return water temperature requirements:
TABLE 9  MINIMUM RETURN WATER TEMPERATURES
Fuel Minimum Return Water Temperature
Natural Gas No minimum return water temperature
Propane No minimum return water temperature
#2 Fuel Oil 140°F (60°C)
B100 Bio-Diesel 100°F (38°C)
#2 Fuel Oil with guaranteed <15
ppm Sulfur (ultra-low sulfur)
100°F (38°C)
Digester Gas/Alternative Fuels Consult Factory
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

Table of Contents