SECTION 4 VTG-IOM-2016-1214 MAINTENANCE
4-11
PROBLEM CAUSE CHECK
Low Air Flow Supply indi-
cated on low air switch
Low Air is annunciated if the airow switch detects
low airow through the boiler.
The air switch has been factory set and should not
be adjusted in the eld.
An extended low air indicaon does not mean that
the low air switch is defecve.
Check that blower is power and feedback plugs are
clipped into the blower.
Check that the burner is clean by observing
through the venturi. Check the blower purge speed
and low re speed is correctly displayed on the
touch screen.
Check for obstrucons in the vent.
Check for obstrucons in the air inlet.
Main ame failure during
ring period
Main gas control valve is de-energized and the con-
trol goes into “lockout” mode. Flame failure occurs
and the indicator is illuminated.
The programmer must be manually reset.
Ignion Failure If UV scanner/ame rod does not detect the ame
during the 4-second trial-for-ignion period, the gas
valve and spark ignion are de-energized. At this
me a safety lockout occurs.
Idenfy and correct.