* Not all points or alarms are available. Availability is completely dependent on job scope and
programming.
031
Boiler 3 Alarm Status
0 - Off
1 On
Binary Input
R
032
Boiler 3 Outlet Temperature
0 to 250
Analog Input
Deg. F
R
033
Boiler 3 Firing Rate
0 to 100
Analog Input
%
R
034
Boiler 4 Local/Remote Switch
0 - Local
1 Remote
Binary Input
R
035
Boiler 4 ModSync Enable/Disable
0 - Disabled
1 Enabled
Binary Input
R
036
Boiler 4 Run Status
0 - Off
1 On
Binary Input
R
037
Boiler 4 Alarm Status
0 - Off
1 On
Binary Input
R
038
Boiler 4 Outlet Temperature
0 to 250
Analog Input
Deg. F
R
039
Boiler 4 Firing Rate
0 to 100
Analog Input
%
R
040
Boiler 5 Local/RemoteSwitch
0 - Local
1 Remote
Binary Input
R
041
Boiler 5 ModSync Enable/Disable
0 - Disabled
1 Enabled
Binary Input
R
042
Boiler 5 Run Status
0 - Off
1 On
Binary Input
R
043
Boiler 5 Alarm Status
0 - Off
1 On
Binary Input
R
044
Boiler 5 Outlet Temperature
0 to 250
Analog Input
Deg. F
R
045
Boiler 5 Firing Rate
0 to 100
Analog Input
%
R
046
Boiler 6 Local/Remote Switch
0 - Local
1 Remote
Binary Input
R
047
Boiler 6 ModSync Enable/Disable
0 - Disabled
1 Enabled
Binary Input
R
048
Boiler 6 Run Status
0 - Off
1 On
Binary Input
R
049
Boiler 6 Alarm Status
0 - Off
1 On
Binary Input
R
050
Boiler 6 Outlet Temperature
0 to 250
Analog Input
Deg. F
R
051
Boiler 6 Firing Rate
0 to 100
Analog Input
%
R
052
Boiler 7 Local/Remote Switch
0 - Local
1 Remote
Binary Input
R
053
Boiler 7 ModSync Enable/Disable
0 - Disabled
1 Enabled
Binary Input
R
054
Boiler 7 Run Status
0 - Off
1 On
Binary Input
R
055
Boiler 7 Alarm Status
0 - Off
1 On
Binary Input
R
056
Boiler 7 Outlet Temperature
0 to 250
Analog Input
Deg. F
R
057
Boiler 7 Firing Rate
0 to 100
Analog Input
%
R
058
Boiler 8 Local/Remote Switch
0 - Local
1 Remote
Binary Input
R
059
Boiler 8 ModSync Enable/Disable
0 - Disabled
1 Enabled
Binary Input
R
060
Boiler 8 Run Status
0 - Off
1 On
Binary Input
R
061
Boiler 8 Alarm Status
0 - Off
Binary Input
R