Chapter 2: Front panel programming 
120  Vigilant VS1 and VS2 Technical Reference Manual 
Event programming 
Panel event programming 
Panel events, such as reset, system startup, and battery low have an event 
notification setting for contact ID, dialer, NET, and printer, which controls where the 
event is sent when it takes place. Each event has a factory default setting that can be 
used with no additional programming. 
Table 33: Default panel event settings 
Panel event  Printer  Dialer  NET  CID 
Aux. power 1 (disable)  Yes  None  No  500 
Aux. power 1 (trouble)  Yes  Acct 1  Yes  312 
Aux. power 2 (disable)  Yes  None  No  500 
Aux. power 2 (trouble)  Yes  Acct 1  Yes  312 
Battery charger (disable)  Yes  None  No  500 
Battery charger (trouble)  Yes  Acct 1  Yes  309 
Battery low (disable)  Yes  None  No  500 
Battery low (trouble)  Yes  Acct 1  Yes  302 
Battery missing (disable)  Yes  None  No  500 
Battery missing (trouble)  Yes  Acct 1  Yes  311 
Clear history  No  Acct 1  Yes  621 
Common alarm  No  Acct 1  Yes  110 
Common disable  No  Acct 1  Yes  500 
Common monitor  No  None  No  140 
Common supervisory  No  Acct 1  Yes  200 
Common trouble  No  None  No  373 
Common trouble for network dialer  No  None  Yes  373 
Common trouble for telco dialer No Acct 1 No 373 
Date No Acct 1 Yes 625 
Dialer disable/remote disconnect  Yes  Acct 1  Yes  551 
Dialer line 1 fault (disable)  Yes  None  No  500 
Dialer line 1 fault (trouble)  Yes  Acct 1  Yes  351 
Dialer line 2 fault (disable)  Yes  None  No  500 
Dialer line 2 fault (trouble)  Yes  Acct 1  Yes  352