Chapter 2: Front panel programming 
Vigilant VS1 and VS2 Technical Reference Manual  51 
Setting up the programmable keys 
There are two control panel buttons that can be assigned to correlation groups in 
order to: 
•  Disable and reenable panel NACs, devices, and zones 
•  Activate panel NACs and devices 
•  Restore panel NACs and devices 
•  Unlatch all output devices globally 
By default, the buttons are not programmed. The buttons can be labeled to indicate 
their function with a slip-in label. To operate the buttons, you must be logged on with 
a level one password or greater. 
Figure 45: Programmable keys 
Key 1
label
Key 1
Key 2
label
Key 2
00:00:00    01/01/07
,
 
Note: You cannot program a key while it is active. If the “Key is active” message is 
displayed, wait until the key deactivates.