Chapter 3: System operation
Vigilant VS1 and VS2 Technical Reference Manual 163
Disabling and enabling the dialer and network
Disabling the dialer, network CMS connection, or any panel or device NACs
configured as City Tie prevents transmission of events to the central monitoring
station (CMS).
When you enable the dialer and network CMS connection:
The Remote Disconnect LED turns off.
The message “Dialer Dsbl/Rem Disc” on the LCD disappears.
The disabled points indicator on the LCD decrements.
The active points indicator on the LCD decrements.
To disable or enable the dialer and network card:
1. Press Remote Disconnect.
2. Enter a level one password.
Initiating a fire drill
Pressing Drill activates all audible and visible notification appliances according to the
panel programming, but does not activate the alarm relay. The Drill LED indicates the
function is active.
Note: Drill will not operate with an active alarm or supervisory event at the panel.
To start and stop a drill:
1. To start a drill, press and hold the Drill button for two seconds.
The Drill button LED turns on indicating that the drill is active, and the control
panel turns on all notification appliance circuits.
2. To stop the drill, press the Drill button again.
The Drill button LED turns off, and the control panel turns off all notification
appliance circuits.
Note: The drill command is also available from the menu, under Control.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Vigilant VS1 and is the answer not in the manual?

GE Security Vigilant VS1 Specifications

General IconGeneral
BrandGE Security
ModelVigilant VS1
CategoryControl Panel
LanguageEnglish

Related product manuals