Chapter 2: Front panel programming
Vigilant VS1 and VS2 Technical Reference Manual 79
To change loop configuration options:
1. Press the menu button and choose Program.
2. Choose Advanced Program.
3. Enter a level two password.
4. Choose Loop Configuration.
5. Program the options.
Main Menu
Reports
Test
Control
Program
⇩
Program
Incremental Program
Auto Program
Advanced Program
⇩
Enter Password
0000
⇩
Advanced Program
Loop Configuration
Panel Configuration
Panel Operation
Correlation group programming
This section includes instructions for:
• Using fast groups
• Adding members to correlation groups
• Enabling in-suite signal silence
• Setting the activation count
• Copying members of a correlation group
• Removing all members from a correlation group
Note: To meet the UL\ULC requirement that evacuation signals activate within 10
seconds, assign sounder base detectors to “fast” correlation groups.
See “Programming fast groups for sounder bases” on page 85.
If you are new to correlation group programming, see “What is a zone?” on page 32.
Adding members to correlation groups
Correlation groups can include zones, NACs, devices, unconfigured alarm events, and
the common trouble event. See the following procedure.