Appendix D: Applications 
250  Vigilant VS1 and VS2 Technical Reference Manual 
Inputs: Zone 1 
Outputs: The polarity reversal or CT1 module labeled ZONE_1 SOUNDERS 
System alarm signaling applications 
What is system alarm signaling? 
In system alarm signaling applications, all sounder bases sound when any alarm 
signal-initiating device is activated. Signal synchronization is required because alarm 
signals are not limited to the same notification zone. 
The sounder bases, once activated, continue to sound an alarm signal until: 
•  Smoke is cleared from the active detectors and the control panel is reset 
•  Signal Silence is pressed 
•  The control panel’s Auto Signal Silence timer expires, if programmed. This can be 
from 5 to 30 minutes 
•  The in-suite signal silence timer expires, if programmed. (See “What is in-suite 
signal silence?” on page 33 and “Programming in-suite signal silence” on page 
83.) 
Typical wiring for system alarm signaling applications 
The figure below shows the typical wiring for synchronized system alarm signaling. 
A  is required to supply power to the sounder bases regardless of riser polarity. 
Typically, the 24 VDC riser that supplies power to the sounder bases is supervised 
using an RM1 Riser Monitor module. You can also use a CT1 module and a PAM-1 
control relay for this purpose. In addition a G1M-RM is required for synchronization.