Appendix D: Applications 
Vigilant VS1 and VS2 Technical Reference Manual  247 
Programming sounder bases for a local alarm signaling 
application 
1.  Set the panel’s Event Notification option to Device 
2.  Configure the smoke detectors as follows: 
Device Type: Smoke or Smoke Heat depending on the detector model 
Message Line 1: SMOKE_<N>, where <N> can be the device address or other 
number 
Base Type: Sounder 
Follow: Head 
3.  Configure the RM1 or CT1 module as follows: 
Device type: Monitor 
Message Line 1: 24VDC_RISER 
Correlated zone and system alarm signaling 
applications 
Correlated signaling applications are those in which sounder bases are triggered by 
associated correlation groups. This includes zone alarm and system alarm signaling 
applications. Detectors are added to the input side, and polarity reversal modules s 
are added to the output side of one or more correlation groups. 
Zone alarm signaling applications 
What is zone alarm signaling? 
In zone alarm signaling applications, detectors and sounder bases are grouped by 
zone. All sounder bases within a zone automatically sound alarm signals when any 
detector in the zone initiates an alarm event. 
Since alarm signals are limited to the same notification zone, signal synchronization 
is not required. The sounder bases, once activated, continue to sound an alarm signal 
until: 
•  Smoke is cleared from the active detectors and the control panel is reset 
•  Signal Silence is pressed 
•  The control panel’s Auto Signal Silence timer expires, if programmed. This can be 
from 5 to 30 minutes