Chapter 3: System operation 
146  Vigilant VS1 and VS2 Technical Reference Manual 
Zone event 
ALRM ACT | 18:00:34 01/01/2007     Z:008 
Zone 08 
Where: 
ALRM ACT = Alarm event 
18:00:34 01/01/2007 = Time and date the event took place 
Z:008 = Zone 08 
Zone 08 = Label (could be the default label or a custom label) 
Device event 
ALRM ACT | 18:00:34 01/01/2007 L:1 D:128 
Loop 1 Device 128 
Where: 
ALRM ACT = Alarm event 
18:00:34 01/01/2007 = Time and date the event took place 
L:1 = Loop 1 
D:128 = Device 128 
Loop 1 Device 128 = Label (could be the default label or a custom label) 
Event ID numbers and descriptions 
Table 40: Event ID numbers and descriptions 
Event ID  Event description    Event ID  Event description 
000  Loop 1 initialization: Loop 1 is 
starting up 
  052  Dialer deliver fail: The dialer failed to 
deliver a message to the receiver or 
CMS 
001  Loop 1 fault: A short or open was 
detected on loop 1 affecting the 
communications between the panel 
and the devices on the loop 
  053  Dialer normal test: A dialer test was 
conducted when the panel was in a 
normal state 
002  Loop 1 map fault: A mapping fault 
was detected on loop 1 while the 
panel was mapping the devices 
  054  Dialer abnormal test: A dialer test 
was conducted when the panel was 
in an off normal state 
003  Loop 1 card fault: The loop 1 card is 
not present or it is not working 
properly 
  055  Dialer configuration: The dialer is not
programmed or has unverified 
changes 
004  Loop 1 uncfgrd alarm: A device on 
loop 1 that is not programmed went 
into alarm 
  056  Net recvr comm fault: 
Communications between the panel 
and the network receiver failed