Chapter 4: Reports 
170  Vigilant VS1 and VS2 Technical Reference Manual 
Walk Test report 
The Walk Test report extracts all test events for the last walk test stored in history. 
Walk test reports can be printed or viewed on the LCD. 
Notes 
•  You cannot view a walk test report while conducting a walk test. 
•  The walk test report includes all events (walk test and all other events) to show 
whether other events occurred during the walk test. 
•  The walk test report cannot be viewed from history after restarting the panel. 
•  To include the activation and restoration of all walk test events in the walk test 
report, the panel must be reset prior to ending the walk test. Once the reset is 
complete, you can end the walk test and view a walk test report. 
To view a Walk Test report: 
1.  Press the menu button and choose Reports. 
2.  Choose Walk Test. 
 
 
Main Menu 
Reports 
Test 
Control 
Program 
⇩ 
Reports 
History 
Walk Test 
Device Maintenance 
Device Maintenance report 
The panel provides a Device Maintenance report of all detectors in the system. The 
report can include: all detectors, all detectors over 20% dirty, or all detectors over 
80% dirty. The report displays the device, along with its dirty percentage and 
sensitivity setting. Device Maintenance reports can be printed or viewed on the LCD.