Appendix D: Applications 
254  Vigilant VS1 and VS2 Technical Reference Manual 
Floor 3 Correlation 
Input   Output  
Floor 3 dwelling and hallway inputs  Floor 3 dwelling and hallway audibles 
No in suite 
signal silence 
Floor 4 correlation 
Input   Output  
Floor 4 dwelling and hallway inputs  Floor 4 dwelling and hallway audibles 
No in suite 
signal silence 
Floor 5 correlation 
Input   Output  
Floor 5 dwelling and hallway inputs  Floor 5 dwelling and hallway audibles 
No in suite 
signal silence 
Creating a hallway correlation 
The hallway correlation ensures that an alarm detected anywhere in the building will 
turn on all audibles located in hallways throughout the building. 
On the input side of this correlation, add all input devices on all floors. Include all 
those inside dwelling units and all those in hallways. 
On the output side, add all hallway sounders throughout the building. 
Notes 
•  Set the alarm activation count for this correlation to 1. 
•  Do not enable in-suite signal silence. 
Hallway Correlation 
Input   Output  
Occupant and hallway inputs on all floors  Hallway sounders on all floors 
Creating an in-suite correlation group 
The in-suite correlation is used to silence sounders inside dwelling units, except on 
the floor of alarm. 
Create one in-suite correlation group. On the input side, add all input devices on all 
floors. Include those located inside dwelling units and those located in hallways. 
On the output side, add all sounders located inside dwelling units on all floors. 
Notes 
•  Set the alarm activation count for this correlation to 1. 
•  For this correlation only, enable in-suite signal silence.