Appendix E: Device types to personality codes correlation 
258  Vigilant VS1 and VS2 Technical Reference Manual 
Model  Device type  Personality code 
CC1S  Continuous Silenceable  (5) Signal - supervised output (Class B) 
CC1S  Genesis Audible Visible Silence  (25) Signal - supervised auto sync output (Class B)
CC1S  Genesis Non-Silenceable  (25) Signal - supervised auto sync output (Class B)
CC1S  Supervised Output  (5) Signal - supervised output (Class B) 
CC1S  Supervised Output (Latched)  (5) Signal - supervised output (Class B) 
CC2  Continuous Non-Silenceable  (7) Riser Selector - supervised output (Class B) 
CC2 Continuous Non-Silenceable 
(Latched) 
(7) Riser Selector - supervised output (Class B) 
CC2  Continuous Silenceable  (7) Riser Selector - supervised output (Class B) 
CC2  Supervised Output  (7) Riser Selector - supervised output (Class B) 
CC2  Supervised Output (Latched)  (7) Riser Selector - supervised output (Class B) 
CR  Relay Non-Silenceable  (8) Signal - dry contact output 
CR  Relay Non-Silenceable (Latched)  (8) Signal - dry contact output 
CR  Relay Silence  (8) Signal - dry contact output 
CR2  Relay Non-Silenceable  (8) Signal - dry contact output 
CR2  Relay Non-Silenceable (Latched)  (8) Signal - dry contact output 
CR2  Relay Silence  (8) Signal - dry contact output 
CRR  Relay Non-Silenceable  (8) Signal - dry contact output 
CRR  Relay Non-Silenceable (Latched)  (8) Signal - dry contact output 
CRR  Relay Silence  (8) Signal - dry contact output 
CT1  Alarm  (1) Alarm - NO latching (Class B) 
CT1  Heat  (1) Alarm - NO latching (Class B) 
CT1  Monitor  (3) Active - NO nonlatching (Class B) 
CT1  Pull Station  (1) Alarm - NO latching (Class B) 
CT1  Remote AC Fail  (3) Active - NO nonlatching (Class B) 
CT1  Remote Drill  (3) Active - NO nonlatching (Class B) 
CT1 Remote Reset  (3) Active - NO nonlatching (Class B) 
CT1  Remote Signal Silence  (3) Active - NO nonlatching (Class B) 
CT1  Smoke  (1) Alarm - NO latching (Class B) 
CT1  Supervisory Latching  (4) Active - NO latching (Class B) 
CT1  Supervisory Nonlatching  (3) Active - NO nonlatching (Class B) 
CT1  Unlatch outputs  (3) Active - NO nonlatching (Class B) 
CT1  Water Flow  (2) Alarm - NO delayed latching (Class B) 
CT2  Alarm  (1) Alarm - NO latching (Class B)