Appendix E: Device types to personality codes correlation
258 Vigilant VS1 and VS2 Technical Reference Manual
Model Device type Personality code
CC1S Continuous Silenceable (5) Signal - supervised output (Class B)
CC1S Genesis Audible Visible Silence (25) Signal - supervised auto sync output (Class B)
CC1S Genesis Non-Silenceable (25) Signal - supervised auto sync output (Class B)
CC1S Supervised Output (5) Signal - supervised output (Class B)
CC1S Supervised Output (Latched) (5) Signal - supervised output (Class B)
CC2 Continuous Non-Silenceable (7) Riser Selector - supervised output (Class B)
CC2 Continuous Non-Silenceable
(Latched)
(7) Riser Selector - supervised output (Class B)
CC2 Continuous Silenceable (7) Riser Selector - supervised output (Class B)
CC2 Supervised Output (7) Riser Selector - supervised output (Class B)
CC2 Supervised Output (Latched) (7) Riser Selector - supervised output (Class B)
CR Relay Non-Silenceable (8) Signal - dry contact output
CR Relay Non-Silenceable (Latched) (8) Signal - dry contact output
CR Relay Silence (8) Signal - dry contact output
CR2 Relay Non-Silenceable (8) Signal - dry contact output
CR2 Relay Non-Silenceable (Latched) (8) Signal - dry contact output
CR2 Relay Silence (8) Signal - dry contact output
CRR Relay Non-Silenceable (8) Signal - dry contact output
CRR Relay Non-Silenceable (Latched) (8) Signal - dry contact output
CRR Relay Silence (8) Signal - dry contact output
CT1 Alarm (1) Alarm - NO latching (Class B)
CT1 Heat (1) Alarm - NO latching (Class B)
CT1 Monitor (3) Active - NO nonlatching (Class B)
CT1 Pull Station (1) Alarm - NO latching (Class B)
CT1 Remote AC Fail (3) Active - NO nonlatching (Class B)
CT1 Remote Drill (3) Active - NO nonlatching (Class B)
CT1 Remote Reset (3) Active - NO nonlatching (Class B)
CT1 Remote Signal Silence (3) Active - NO nonlatching (Class B)
CT1 Smoke (1) Alarm - NO latching (Class B)
CT1 Supervisory Latching (4) Active - NO latching (Class B)
CT1 Supervisory Nonlatching (3) Active - NO nonlatching (Class B)
CT1 Unlatch outputs (3) Active - NO nonlatching (Class B)
CT1 Water Flow (2) Alarm - NO delayed latching (Class B)
CT2 Alarm (1) Alarm - NO latching (Class B)