Chapter 2: Front panel programming
82 Vigilant VS1 and VS2 Technical Reference Manual
To set the activation count:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2
password.
3 Choose Loop Configuration.
4. Choose Correlation Groups and enter the number of
the correlation group to be programmed. (Values
range from 001 to 199.)
5. Choose Activation Count and enter the activation
count (values range from 01 to 99).
6. Choose Save.
Advanced Program
Loop Configuration
Loop Configuration
Loop Class
Zone
Correlation Groups
Correlation Groups
Number 001<>
Correlation Group 001
Add/Remove Device
Suite Sig Sil No
Activation Count
Activation Count
Number 01
Save
To copy the members of a correlation group:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2
password.
3 Choose Loop Configuration.
4. Choose Correlation Groups.
5. Enter the number of the correlation group to be
programmed. (Values range from 001 to 199.)
6. Choose Copy and enter the number of the correlation
group to be copied.
7. Choose Save.
Advanced Program
Loop Configuration
Loop Configuration
Loop Class
Zone
Correlation Groups
Correlation Groups
Number 003<>
Correlation Group 003
Add/Remove Device
Suite Sig Sil No
Activation Count
Copy
Copy
From Group 001<>
Save

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Security Vigilant VS1 and is the answer not in the manual?

GE Security Vigilant VS1 Specifications

General IconGeneral
BrandGE Security
ModelVigilant VS1
CategoryControl Panel
LanguageEnglish

Related product manuals