EasyManua.ls Logo

GE DR60 - Analog Acquisition; Voltage Inputs

GE DR60
124 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DR60
DR60-TM-EN-2A
110
1.6 Analog Acquisition
Analog Acquisition
Resolution
16 bits
Frequency measurement range
15 Hz to 70 Hz
System Frequency
Bandwidth (frequency response)
50 Hz at 256 ppc
DC to 3,2 kHz
60 Hz at 256 ppc
DC to 3,8 kHz
50 Hz at 512 ppc
DC to 10 kHz
60 Hz at 512 ppc
DC to 10 kHz
1.7 Voltage Inputs
Voltage inputs specifications (50/60 Hz)
Characteristic
Standard Input
High Accuracy Inputs
Nominal Voltage (
)
115 V
115V
Voltage range RMS
0.25-460 V
0.11-230 V
Analog Input Accuracy
Class 0.5 (IEC 61869-2)
<0,1% of full scale
Class 0.1 (IEC 61869-2)
<0,1% of full scale
Impedance
> 210
> 420
Burden V
n
< 0.1 VA
< 0.1 VA
Continuous Overload
230 V (2 x
)
230 V (2 x
)
Maximum Overload (1 s)
460 V (4 x
)
460 V (4 x
)
Input Isolation
>3,5 kV
>3,5 kV

Table of Contents