DR60
71
DR60
Digital Recorder
Chapter 6: PMU
This chapter provides detailed information about the PMU feature.
1 Synchrophasor Measurement and Broadcast
The DR60 provides powerful and cost-effective synchrophasor measurement solution
according to IEEE C37.118.1/2-2011/1a-2014 standards and is capable of transmitting
synchrophasors in up to 4 separate data streams. Each stream can be configurable
independently based on: contents; frame rate; performance class (P or M) and
communication mode (TCP or UDP).
1.1 Reported Values
Reported values
Phasors
Voltage synchrophasors (any phase)
Current synchrophasors (any phase)
Positive and Negative sequence for voltage
circuits
Positive and Negative sequence for current
circuits
Frequency
Frequency and frequency variation of one circuit
1.2 Accuracy Limits
The Total Vector Error defined through