DR60
68
COMTRADE records in the DR60 are comprised by the “.cfg” and “.dat” files described in
the standard.
6.2 Record Naming
Records are named using the COMNAME methodology, according to IEEE C37.232-
2011, Common Format for Naming Time Sequence Data Files (COMNAME).
Fault, Disturbance, Steady-state, and Sequence of Events records are named as follows:
STARTDATE,STARTTIME,TIMECODE,STATIONID,DEVICEID,COMPANY,DURATION.CFG
STARTDATE,STARTTIME,TIMECODE,STATIONID,DEVICEID,COMPANY,DURATION.DAT
The table below describe each parameter in the file name.
Parameter
Format
Description
STARTDATE
yymmdd
Record’s start date
(year, mounth, day)
STARTTIME
hhmmssuuuuuu
Record’s start time
(hour, minutes, seconds,
microsseconds)
TIMECODE
soohmm
Indication of timezone offset
(the last three characters are
included only when fractional hours
are in use)
STATIONID
Location of the equipment,
configurable in:
GENERAL > LOCATION
(up to 255 characters)
DEVICEID
Equipment identifier, configurable
in:
GENERAL > IDENTIFIER
(up to 61 characters)
COMPANY
Equipment owner description,
configurable in:
GENERAL > OWNER
(up to 255 characters)