Loading...
DR60
DR60-TM-EN-2A
116
Conducted emission
Class A
0,15 MHz to 0,50 MHz
79 dB(µV) quasi peak
66 dB(µV) average
0,5 MHz to 30 MHz
73 dB(µV) quasi peak
60 dB(µV) average
1.14 Safety Tests
Safety tests
Safety
IEC 60255-27:2014
IEC 60255-5
Inpulse - 5KV
Dielectric withstand - 3,3KVDC for 60 seconds
Insulation > 100M Ω
1.15 Environmental tests
Environmental tests
Cold
IEC 60068-2-
1
-40°C, 16 hours
Dry heat
IEC 60068-2-
2
+55°C, 16 hours
Damp heat
IEC 60068-2-
30
95% no condensation, 55°C (Damp heat)
Change of
temperature
IEC 60068-2-
14
-40°C to 55ºC / 9 hours / 2 cycles
Vibration
IEC 60255-
21-1
Class 2

Table of Contents