Serial communication port
2 Communication Ports and Protocols
The DR60 web interface was designed using the GE Predix UI platform and it can be
accessed using Mozilla Firefox or Google Chrome browser from computers, cellphones
or tablet.
The web interface uses the follow ports and protocols. These ports must be properly
configured in the routers and firewalls for the communication work completely.
Port
Protocol
Use
22
SFTP
Download COMTRADE files
22
SSH
Configuration download and upload,
logs download and firmware upgrade
443
HTTPS
Web monitoring interface
102
MMS
MMS Report control block
4220
UDP/IP
IP recovery tool Ethernet 1
4221
UDP/IP
IP recovery tool Ethernet 2
502
TCP
MODBUS interface
20000
DNP3
DNP3 transmission
4712-4732
PMU
C37.118.2-2011 PMU transmission

Table of Contents