Signal Name Source Destination Description
BARCB2 Autoreclose Lockout (55) Leader/Follower (7) Block Autoreclose for CB2
CB13PDTComp 3-phase AR Dead Time (25)
CB Autoclose (32)
Prepare Reclaim Initiation (34)
CB Healthy and System Check Timers (39)
Three-pole Autoreclose dead time is
complete for CB1
CB13PFTComp
Follower 3-phase CB AR
Time (29)
CB Autoclose (32)
Prepare Reclaim Initiation (34)
CB Healthy and System Check Timers (39)
Three-pole Autoreclose follower time is
complete for CB1
CB1ARSucc Successful AR Signals (36)
AR Reset Successful (37)
CB1 AR In Progress (16)
Autoreclose successful for CB1
CB1FARIP CB1 AR In Progress (16)
Autoreclose Lockout (55)
Reclaim Time (35)
Autoreclose in progress for CB1 acting as
follower
CB1LARIP CB1 AR In Progress (16)
Autoreclose Lockout (55)
Reclaim Time (35)
Autoreclose in progress for CB1 acting as
leader
CB1OP1P CB Open (3)
Dead Time Start Enable (22)
Follower 1-phase CB AR Time (28)
CB Autoclose (32)
Successful AR Signals (36)
CB1 is open on 1 phase
CB1OP2/3P CB Open (3)
CB1 AR In Progress (16)
3-phase AR cycle selection (21)
Follower 1-phase CB AR Time (28)
Successful AR Signals (36)
CB1 is open on 2 or 3 phases
CB1OPAny CB Open (3) Autoreclose Lockout (55) CB1 is open on 1, 2 or 3 phases
CB1SPOK
CB1 is OK for single-phase autoreclosure
(either as leader or follower)
CB1CRLo CB In Service (4) Reset CB Lockout (57) Reset CB1 lockout
CB1F3PAR
3-phase AR cycle selection
(21)
Follower 3-phase CB AR Time (29)
CB Autoclose (32)
Three-phase Autoreclose is active for CB1
as follower
CB1F3PAROK AR Modes Enable (9)
CB1 AR In Progress (16)
3-phase AR cycle selection (21)
Autoreclose Lockout (55)
CB1 is OK to perform three-phase
Autoreclose as follower
CB1FSPAR
1-phase AR Cycle Selection
(19)
Follower CB AR Enable (27
Follower 1-phase CB AR Time (28)
Follower 3-phase CB AR Time (29)
CB Autoclose (32)
Single-phase Autoreclose is in progress for
CB1 as follower
CB1FSPAROK AR Modes Enable (9)
Force 3-phase Trip (10), 1-phase AR Cycle
Selection (19)
3-phase AR cycle selection (21)
Autoreclose Lockout (55)
CB1 is OK to perform single-phase
Autoreclose as follower
CB1L3PAR
3-phase AR cycle selection
(21)
1-phase AR Cycle Selection (19)
3-phase AR Dead Time (25)
CB Autoclose (32)
CB Healthy and System Check Timers (39)
Three-phase Autoreclose is active for CB1
(CB1 as leader)
CB1L3PAROK AR Modes Enable (9)
CB1 AR In Progress (16)
3-phase AR cycle selection (21),
Autoreclose Lockout (55)
CB1 is OK to perform three-phase
Autoreclose (as leader)
CB1LFRC
Leader/Follower
Logic 1 & 2 (7)
Leader/Follower
Logic 1 & 2 (7)
Follower 1-phase CB AR Time (28)
Follower 3-phase CB AR Time (29)
Reclaim Time (35)
CB1 failed to reclose (as leader)
P446SV Chapter 11 - Autoreclose
P446SV-TM-EN-1 273