5.24.3 CB MANUAL CLOSE SYSTEM CHECK LOGIC DIAGRAM
V03375
Note: If the DDB signal CB1 Ext CS OK is not mapped in PSL , it
defaults to High .
CB1M SC CS1
Enabled
CB1M SC CS2
Enabled
CB1 CS1 OK
CB1M SC DLLB
Enabled
CB1M SC LLDB
Enabled
CB1M SC required
Disabled
CB1 CS2 OK
Dead Line
Live Bus 1
Live Line
&
1
CB1 Man SCOK
&
&
&
&
CB1M SC DLDB
Enabled
Dead Bus 1
&
Dead Line
Dead Bus 1
CB1 Ext CS OK
Note: If the DDB signal CB2 Ext CS OK is not mapped in PSL , it
defaults to High.
CB2M SC CS1
Enabled
CB2M SC CS2
Enabled
CB2 CS1 OK
CB2M SC DLLB
Enabled
CB2M SC LLDB
Enabled
CB2M SC required
Disabled
CB2 CS2 OK
Dead Line
Live Bus 2
Live Line
&
1
CB2 Man SCOK
&
&
&
&
CB2M SC DLDB
Enabled
Dead Bus 2
&
Dead Line
Dead Bus 2
CB2 Ext CS OK
883
884
889
886
888
887
889
887
900
1577
1463
889
1461
888
1462
1462
889
901
1458
1574
Figure 196: CB Manual Close System Check Logic Diagram (Modules 51 & 52)