13 OUT OF STEP PROTECTION
For this test, an injection set with a state sequencer function is required, as dynamic impedance conditions are
going to be tested. The four states impedances that applied during the Out of Step commissioning process are
shown below:
V01451
R
Z5
Z6
Z5'
Z6'
R5 R6R5'R6'
+jX
R
State 1
State 2
State 3
State 4
Figure 301: State impedances
Depending on the Out of Step (OST) settings, use one of the following setting options.
OST setting
Predictive OST setting
Predictive and OST setting
13.1
OST SETTING
1. Clear all alarms.
2. Set the OST timer to zero.
3. To test OST, a 4-state test sequence is required. Based on healthy voltages (VA = VB = VC = 57.8 V) calculate
the currents to generate the impedances as below.
State 1
State 2 State 3 State 4
Applied current
(all 3 phases)
57.8/(1.1R6) 57.8/(R5+0.5(R6-R5)) 57.8/(0.95R5) 57.8/(1.1R5')
Angle 180°
Duration 500 ms Longer than ‘Delta t’ set time 100 ms 500 ms
Now apply the 4-state sequence, check that all 3-phases have tripped and that an OST alarm is displayed on the
local LCD.
Chapter 24 - Commissioning Instructions P446SV
646 P446SV-TM-EN-1