EasyManua.ls Logo

GE MiCOM P40

GE MiCOM P40
962 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E00800
IED
S F
V
RES
=
Z
S0
2Z
S1
+ Z
S0
+ 2Z
L1
+ Z
L0
X 3 E
E
Z
S
Z
L
V
A
V
A
V
A
V
A
V
C
V
C
V
C
V
C
V
C
V
C
V
B
V
B
V
B
V
B
V
B
V
B
V
RES
V
RES
Figure 220: Residual voltage for a solidly earthed system
As can be seen from the above diagram, the residual voltage measured on a solidly earthed system is solely
dependent on the ratio of source impedance behind the protection to the line impedance in front of the protection,
up to the point of fault. For a remote fault far away, the Z
S
/Z
L
: ratio will be small, resulting in a correspondingly
small residual voltage. Therefore, the protection only operates for faults up to a certain distance along the system.
The maximum distance depends on the device setting.
5.3.2
CALCULATION FOR IMPEDANCE EARTHED SYSTEMS
Consider a Phase-A to Earth fault on a simple radial system.
P446SV Chapter 14 - Voltage Protection Functions
P446SV-TM-EN-1 397

Table of Contents

Related product manuals