for the next dead time to start when conditions are suitable. The operation also resets the signal that would set the
circuit breaker to close, and stops and resets the reclaim timer. The reclaim time starts again if the signal to set a
circuit breaker to close goes high following completion of a dead time in a subsequent Autoreclose cycle.
If the circuit breaker is closed and has not tripped again when the reclaim time expires, signals are generated to
indicate successful Autoreclose. These signals increment the relevant circuit breaker successful Autoreclose shot
counters and reset the relevant Autoreclose in progress signal.
The “successful Autoreclose” signals generated from the logic can be reset by various commands and settings
options available under CB CONTROL menu settings as follows:
If Res AROK by UI is set to Enabled, all the signals can be reset by user interface command Reset AROK Ind from
the CB CONTROL menu.
If Res AROK by NoAR is set to Enabled, the signals for each circuit breaker can be reset by temporarily
generating an Autoreclose disabled signal according to the logic shown.
If Res AROK by Ext is set to Enabled, the signals can be reset by activation of an external input signal
appropriately mapped in the PSL.
If Res AROK by TDly is set to Enabled, the signals are automatically reset after a time delay set in AROK Reset
Time.
5.14.1
PREPARE RECLAIM INITIATION LOGIC DIAGRAM
V03353
R
Q
S
Set CB1 Close
CB13PDTComp
CB1SPDTComp
CB1SPFTComp
CB1 Fast SCOK
CB1L SCOK
OK Time 3P
CB1F SCOK
CB13PFTComp
1
&
SETCB1SPCl
&
&
&
1
R
Q
S
&
SETCB13PCl
R
Q
S
Set CB2 Close
CB23PDTComp
CB2SPDTComp
CB2SPFTComp
CB2 Fast SCOK
CB2L SCOK
OK Time 3P
CB2F SCOK
CB23PFTComp
1
&
SETCB2SPCl
&
&
&
1
R
Q
S
&
SETCB23PCl
1565
1573
1572
1555
1491
1449
1455
1454
1555
1456
Figure 175: Prepare Reclaim Initiation logic diagram (Module 34)