5.3.1 CIRCUIT BREAKER IN SERVICE LOGIC DIAGRAM
CB1 AR Lockout
&
CB1 Closed 3 ph
1
CB1CRLO
V03303
Num CBs
CB1 Only
Both CB1&CB2
&
CBIST
0
CBIST
CBISMT
&
R
Q
S
1
CB1 In Service
Logic 1
CB1 ARIP
CB2 AR Lockout
&
CB2 Closed 3 ph
1
CB2CRLO
Num CBs
CB2 Only
Both CB1&CB2 &
CBIST
0
CBIST
CBISMT &
R
Q
S
1
CB2 In Service
Logic 1
CB2 ARIP
Figure 151: CB In Service logic diagram (Module 4)
5.4
AUTORECLOSE ENABLE LOGIC
The Autoreclose function must be enabled in the CONFIGURATION column before it can be brought into service. It
can be brought into service by:
using an opto-input mapped to the AR Enable DDB signal
pulsing the DDB signal AR On Pulse (use AR Off Pulse to bring it out of service)
programming a function key on the HMI.
if applicable, using IEC 60870-5-103 communications
Further validation signals are also required to switch on Autoreclose. These are the DDB signals AR Enable CB1
and AR Enable CB2. Once Autoreclose is in service, the AR In Service DDB signal is asserted and the AR Status cell
in the CB CONTROL column is set accordingly.
5.4.1
AUTORECLOSE ENABLE LOGIC DIAGRAM
V03301
Auto-Reclose
Enable
&
AR On Pulse
AR OFF Pulse
Autoreclose
Status
Default = ON
1
AR Enable
AR Enable CB1
AR Enable CB2
1
AR DISABLED
AR In Service
*Defaults to High if not mapped in PSL
HMI Comand
IEC 60870 Comand
*
*
1382
1383
1384
1609
1605
1385
Figure 152: Autoreclose Enable logic diagram (Module 5)
5.5
AUTORECLOSE LEADER/FOLLOWER
You can select either CB1 or CB2 to be the leader, with CB2 or CB1 as the follower respectively.
Chapter 11 - Autoreclose P446SV
292 P446SV-TM-EN-1

Table of Contents