Appendix B -Settings and Signals 
 
 
 
MENU TEXT  COL  ROW  DEFAULT SETTING  AVAILABLE OPTIONS 
DESCRIPTION 
I>2 Function  35  0B  IEC S Inverse 
IEC S Inverse 
IEC V Inverse 
IEC E Inverse 
UK LT Inverse 
IEEE M Inverse 
IEEE V Inverse 
IEEE E Inverse 
US Inverse 
US ST Inverse 
Setting for the tripping characteristic for the second stage overcurrent element. 
I>2 Direction  35  0C  Non-Directional 
Directional Fwd 
Directional Rev 
This setting determines the direction of measurement for second stage element. 
I>2 Current Set  35  0D  1 
From 0.08*I1 to 4.0*I1 in steps of 0.01*I1 
[Courier Number (current)] 
Pick-up setting for second stage overcurrent element. 
I>2 Time Delay  35  0E  1 
From 0 to 100 in steps of 0.01 
[Courier Number (time-seconds)] 
Setting for the time-delay for the definite time setting if selected for second stage element. The setting is visible only when DT function is 
selected. 
I>2 TMS  35  0F  1 
From 0.025 to 1.2 in steps of 0.005 
[Courier Number (decimal)] 
Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic. 
I>2 Time Dial  35  10  1 
From 0.01 to 100 in steps of 0.01 
[Courier Number (decimal)] 
Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves. The Time Dial (TD) is a multiplier on the 
standard curve equation, in order to achieve the required tripping time. The reference curve is based on TD = 1.  
Care: Certain manufacturer's use a mid-range value of TD = 5 or 7, so it may be  necessary to divide by 5 or 7 to achieve parity. 
I>2 Reset Char  35  11  DT 
Inverse 
Setting to determine the type of reset/release characteristic of the IEEE/US curves. 
I>2 tRESET  35  12  0 
From 0 to 100 in steps of 0.01 
[Courier Number (time-seconds)] 
Setting that determines the reset/release time for definite time reset characteristic 
I>3 Status  35  13  Disabled 
Enabled 
Enabled VTS 
Enabled Ch Fail 
En VTSorCh Fail 
En VTSandCh Fail 
Setting that defines third stage overcurrent operating status. Depending of this setting, I>3 will be enabled permanently or in case of Voltage 
Transformer Supervision (fuse fail) operation, or in case of communication channel fail, or a combination (and /or) of both. 
I>3 Current Set  35  15  10 
From 0.08*I1 to 32*I1 in steps of 0.01*I1 
[Courier Number (current)] 
Pick-up setting for third stage overcurrent element. 
I>3 Time Delay  35  16  0 
From 0 to 100 in steps of 0.01 
[Courier Number (time-seconds)] 
Setting for the operating time-delay for third stage overcurrent element. 
I>4 Status  35  18  Disabled 
Enabled 
Enabled VTS 
Enabled Ch Fail 
En VTSorCh Fail 
En VTSandCh Fail