P446SV
Appendix B -Settings and Signals
P446SV-TM-EN-1
B113
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves.
I2>1 Reset Char 36 1C DT
DT
Inverse
[Indexed String]
Setting to determine the type of reset/release characteristic of the IEEE/US curves.
I2>1 tRESET 36 1D 0
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Setting that determines the reset/release time for definite time reset characteristic.
I2>2 Status 36 20 Disabled
Disabled
Enabled
[Indexed String]
Setting to enable or disable the second stage negative sequence element.
I2>2 Function 36 21 DT
DT
IEC S Inverse
IEC V Inverse
IEC E Inverse
UK LT Inverse
IEEE M Inverse
IEEE V Inverse
IEEE E Inverse
US Inverse
US ST Inverse
[Indexed String]
Setting for the tripping characteristic for the second stage negative sequence overcurrent element.
I2>2 Direction 36 22 Non-Directional
Non-Directional
Directional Fwd
Directional Rev
[Indexed String]
This setting determines the direction of measurement for this element.
I2>2 Current Set 36 25 0.2
From 0.08*I1 to 4*I1 in steps of 0.01*I1
[Courier Number (current)]
Pick-up setting for the second stage negative sequence overcurrent element.
I2>2 Time Delay 36 27 10
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Setting for the operating time-delay for the second stage negative sequence overcurrent element.
I2>2 TMS 36 28 1
From 0.025 to 1.2 in steps of 0.005
[Courier Number (decimal)]
Setting for the time multiplier setting to adjust the operating time of the IEC IDMT characteristic.
I2>2 Time Dial 36 29 1
From 0.01 to 100 in steps of 0.01
[Courier Number (decimal)]
Setting for the time multiplier setting to adjust the operating time of the IEEE/US IDMT curves.
I2>2 Reset Char 36 2C DT
DT
Inverse
[Indexed String]
Setting to determine the type of reset/release characteristic of the IEEE/US curves.
I2>2 tRESET 36 2D 0
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Setting that determines the reset/release time for definite time reset characteristic.
I2>3 Status 36 30 Disabled
Disabled
Enabled
[Indexed String]
Setting to enable or disable the third stage negative sequence element.
I2>3 Direction 36 32 Non-Directional
Non-Directional
Directional Fwd
Directional Rev
[Indexed String]
This setting determines the direction of measurement for this element.
I2>3 Current Set 36 35 0.2
From 0.08*I1 to 32*I1 in steps of 0.01*I1
[Courier Number (current)]
Pick-up setting for the third stage negative sequence overcurrent element.