Appendix B -Settings and Signals
P446SV
B124
P446SV-TM-EN-1
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
twice in each swing cycle, and a short setting ensures continued PSB pick-up, to ride through the gaps.
OST Mode 3D 23 OST Disabled
OST Disabled
OST Predictive Trip
OST Trip
[Indexed String]
To enable (activate) or disable (turn off) Out of Step protection. This setting (and all related settings below) is invisible if PowerSwing Block is
disabled in ‘CONFIGURATION’ column.
If ‘OST Trip’ is selected, relay will operate after Tost time delay if the measured positive sequence impedance has passed the Z6-Z5 region
slower than 25 ms (@ 50 or 60 Hz) and if the polarity of the resistive component has changed between entering and exiting zone 5.
If ‘Predictive OST Trip’ is selected, relay will operate after Tost time delay if the positive sequence impedance has passed the Z6-Z5 region
faster than 25ms but slower than ‘Delta t’ set time.
If ‘Predictive & OST Trip’ is selected, it will operate if any of two above criteria is satisfied.
Z5 3D 24 30
From 0.1 to 500 in steps of 0.01
[Courier Number (impedance)]
Setting for Z5 forward reactance reach.
Z6 3D 25 32
From 0.1 to 500 in steps of 0.01
[Courier Number (impedance)]
Setting for Z6 forward reactance reach.
Z5' 3D 26 -30
From -500 to -0.1 in steps of 0.01
[Courier Number (impedance)]
Setting for Z5 reverse reactance reach.
Z6' 3D 27 -32
From -500 to -0.1 in steps of 0.01
[Courier Number (impedance)]
Setting for Z6 reverse reactance reach.
R5 3D 28 20
From 0.1 to 200 in steps of 0.01
[Courier Number (impedance)]
Setting for Z5 positive resistive reach.
R6 3D 29 22
From 0.1 to 200 in steps of 0.01
[Courier Number (impedance)]
Setting for Z6 positive resistive reach.
R5' 3D 2A -20
From -0.1 to -200 in steps of 0.01
[Courier Number (impedance)]
Setting for Z5 negative resistive reach.
R6' 3D 2B -22
From -0.1 to -200 in steps of 0.01
[Courier Number (impedance)]
Setting for Z6 negative resistive reach.
Blinder Angle 3D 2C 80
From 20 to 90 in steps of 1
[Courier Number (angle)]
Setting of blinder angle, common for both Z5 and Z6.
delta T 3D 2D 0.04
From 0.04 to 1 in steps of 0.001
[Courier Number (time-seconds)]
Time setting that is compared with the measured time between positive sequence impedance entering Z6 and entering Z5.
Tost 3D 2E 0
From 0 to 1 in steps of 0.01
[Courier Number (time-seconds)]
Tripping time delay common for any OST setting option.
GROUP 1: VOLT
PROTECTION
42 00
This column contains settings for Voltage protection
UNDER VOLTAGE
42
01
V< Measur't Mode 42 02 V<1 & V<2 Ph-Ph
V<1 & V<2 Ph-Ph
V<1 & V<2 Ph-N
V<1Ph-Ph V<2Ph-N
V<1Ph-N V<2Ph-Ph
[Indexed String]
Sets the combination of measured input voltage that will be used for the undervoltage elements.
Note: If any stage is disabled, the associated text in the setting menu cell setting will remain visible but will not affect the operation of the
stage that is enabled.
V< Operate Mode 42 03 V<1 & V<2 Any Ph
V<1 & V<2 Any Ph
V<1 & V<2 3 Phase