Appendix B -Settings and Signals
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
This setting enables CB1 to close by manual control when the live line & dead bus1 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB1M SC DLDB 48 B7 Disabled
Enabled
This setting enables CB1 to close by manual control when the dead line & dead bus1 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB2M SC required 48 B8 Disabled
Enabled
This setting determines whether a system check (e.g. live bus / dead line etc) is required for any manual (operator-controlled) closure of CB2.
If Enabled, system check is required for closure. If Disabled, system check is not required.
CB2M SC CS1 48 B9 Disabled
Enabled
This setting enables CB2 to close by manual control when system satisfies all the System Check Synchronism Stage 1 conditions as listed
under the setting CB2 CS1 Status in the SYSTEM CHECKS column.
CB2M SC CS2 48 BA Disabled
Enabled
This setting enables CB2 to close by manual control when the system satisfies all the System Check Synchronism Stage 2 conditions as listed
under setting CB2 CS2 status in the SYSTEM CHECKS column.
CB2M SC DLLB 48 BB Disabled
Enabled
This setting enables CB2 to close by manual control when the dead line & live bus2 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB2M SC LLDB 48 BC Disabled
Enabled
This setting enables CB2 to close by manual control when the live line & dead bus2 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB2M SC DLDB 48 BD Disabled
Enabled
This setting enables CB2 to close by manual control when the dead line & dead bus2 conditions are satisfied as set in the SYSTEM CHECKS
column.
49 00
This column contains settings for Autoreclose
Num CBs 49 50 CB1 Only
CB2 Only
CB1&CB2
Setting defines which CB(s) are active for the specific installation: CB1 only, CB2 only or both CB1 & CB2.
AR Mode 49 51 AR 3P
1/3P
3P
AR Opto
If the Num CBs setting (cell 4950 {above} in the AUTORECLOSE column) is set to CB1 Only, or CB2 Only, then this setting determines which
auto-reclose modes are permitted for the circuit breaker : single phase (AR 1P) only, both single phase and three phase (AR 1/3P), three phase
only (AR 3P), or the auto-reclosing mode is controlled by opto input signals (AR Opto) mapped via DDBs (1497) AR Mode 1P and (1498) AR
Lead/Foll ARMode 49 53 L 3P, F 3P
L 1P, F 3P
L 3P, F 3P
L 1/3P, F 1/3P
L 1/3P, F 3P