Appendix B -Settings and Signals
P446SV-TM-EN-1
B135
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
[Indexed String]
This setting enables CB1 to close by manual control when the live line & dead bus1 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB1M SC DLDB 48 B7 Disabled
Disabled
Enabled
[Indexed String]
This setting enables CB1 to close by manual control when the dead line & dead bus1 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB2M SC required 48 B8 Disabled
Disabled
Enabled
[Indexed String]
This setting determines whether a system check (e.g. live bus / dead line etc) is required for any manual (operator-controlled) closure of CB2.
If Enabled, system check is required for closure. If Disabled, system check is not required.
CB2M SC CS1 48 B9 Disabled
Disabled
Enabled
[Indexed String]
This setting enables CB2 to close by manual control when system satisfies all the System Check Synchronism Stage 1 conditions as listed
under the setting CB2 CS1 Status in the SYSTEM CHECKS column.
CB2M SC CS2 48 BA Disabled
Disabled
Enabled
[Indexed String]
This setting enables CB2 to close by manual control when the system satisfies all the System Check Synchronism Stage 2 conditions as listed
under setting CB2 CS2 status in the SYSTEM CHECKS column.
CB2M SC DLLB 48 BB Disabled
Disabled
Enabled
[Indexed String]
This setting enables CB2 to close by manual control when the dead line & live bus2 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB2M SC LLDB 48 BC Disabled
Disabled
Enabled
[Indexed String]
This setting enables CB2 to close by manual control when the live line & dead bus2 conditions are satisfied as set in the SYSTEM CHECKS
column.
CB2M SC DLDB 48 BD Disabled
Disabled
Enabled
[Indexed String]
This setting enables CB2 to close by manual control when the dead line & dead bus2 conditions are satisfied as set in the SYSTEM CHECKS
column.
GROUP 1:
AUTORECLOSE
49 00
This column contains settings for Autoreclose
Num CBs 49 50 CB1 Only
CB1 Only
CB2 Only
CB1&CB2
[Courier Number]
Setting defines which CB(s) are active for the specific installation: CB1 only, CB2 only or both CB1 & CB2.
AR Mode 49 51 AR 3P
1P
1/3P
3P
AR Opto
[Indexed String]
If the Num CBs setting (cell 4950 {above} in the AUTORECLOSE column) is set to CB1 Only, or CB2 Only, then this setting determines which
auto-reclose modes are permitted for the circuit breaker : single phase (AR 1P) only, both single phase and three phase (AR 1/3P), three phase
only (AR 3P), or the auto-reclosing mode is controlled by opto input signals (AR Opto) mapped via DDBs (1497) AR Mode 1P and (1498) AR
Mode 3P.
Lead/Foll ARMode 49 53 L 3P, F 3P
L 1P, F 1P
L 1P, F 3P
L 3P, F 3P
L 1/3P, F 1/3P
L 1/3P, F 3P
AR Opto