GE Power Management PQM Power Quality Meter 7-39
7 MODBUS COMMUNICATIONS 7.3 MODBUS MEMORY MAP
7
EVENT
RECORD
continued
0B0C Record #N Sc (low) --- --- 0.01 x kVA F3 N/A
0B0D Record #N PFc --- --- 0.01 x PF F2 N/A
0B0E Record #N P3 (high) --- --- 0.01 x kW F4 N/A
0B0F Record #N P3 (low) --- --- 0.01 x kW F4 N/A
0B10 Record #N Q3 (high) --- --- 0.01 x kvar F4 N/A
0B11 Record #N Q3 (low) --- --- 0.01 x kvar F4 N/A
0B12 Record #N S3 (high) --- --- 0.01 x kVA F3 N/A
0B13 Record #N S3 (low) --- --- 0.01 x kVA F3 N/A
0B14 Record #N PF3 --- --- 0.01 x PF F2 N/A
0B15 Record #N Frequency --- --- 0.01 x Hz F1 N/A
0B16 Record #N Positive kWh (high) --- --- kWh F3 N/A
0B17 Record #N Positive kWh (low) --- --- kWh F3 N/A
0B18 Record #N Negative kWh (high) --- --- kWh F3 N/A
0B19 Record #N Negative kWh (low) --- --- kWh F3 N/A
0B1A Record #N Positive kvarh (high) --- --- kvarh F3 N/A
0B1B Record #N Positive kvarh (low) --- --- kvarh F3 N/A
0B1C Record #N Negative kvarh (high) --- --- kvarh F3 N/A
0B1D Record #N Negative kvarh (low) --- --- kvarh F3 N/A
0B1E Record #N kVAh (high) --- --- kVAh F3 N/A
0B1F Record #N kVAh (low) --- --- kVAh F3 N/A
0B20 Record #N Ia Demand --- --- A F1 N/A
0B21 Record #N Ib Demand --- --- A F1 N/A
0B22 Record #N Ic Demand --- --- A F1 N/A
0B23 Record #N In Demand --- --- A F1 N/A
0B24 Record #N P3 Demand (high) --- --- 0.01 x kW F4 N/A
0B25 Record #N P3 Demand (low) --- --- 0.01 x kW F4 N/A
0B26 Record #N Q3 Demand (high) --- --- 0.01 x kvar F4 N/A
0B27 Record #N Q3 Demand (low) --- --- 0.01 x kvar F4 N/A
0B28 Record #N S3 Demand (high) --- --- 0.01 x kVA F3 N/A
0B29 Record #N S3 Demand (low) --- --- 0.01 x kVA F3 N/A
0B2A Record #N Ia THD --- --- 0.1 x % F1 N/A
0B2B Record #N Ib THD --- --- 0.1 x % F1 N/A
0B2C Record #N Ic THD --- --- 0.1 x % F1 N/A
0B2D Record #N In THD --- --- 0.1 x % F1 N/A
0B2E Record #N Van THD --- --- 0.1 x % F1 N/A
0B2F Record #N Vbn THD --- --- 0.1 x % F1 N/A
0B30 Record #N Vcn THD --- --- 0.1 x % F1 N/A
0B31 Record #N Vab THD --- --- 0.1 x % F1 N/A
0B32 Record #N Vbc THD --- --- 0.1 x % F1 N/A
0B33 Record #N Analog Input (high) --- --- --- F3 N/A
0B34 Record #N Analog Input (low) --- --- --- F3 N/A
0B35 Record #N Trace Memory Trigger Cause --- --- --- F41 N/A
0B36 Record #N Internal Fault Error Code --- --- --- F108 N/A
0B37 Reserved
Table 7–10: PQM MEMORY MAP (Sheet 25 of 40)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS and
SCALE
FORMAT FACTORY DEFAULT
Notes: * Data type depends on the Command Operation Code. ** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”. **** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.

Table of Contents

Questions and Answers: