GE Power Management PQM Power Quality Meter 7-41
7 MODBUS COMMUNICATIONS 7.3 MODBUS MEMORY MAP
7
METER ID
continued
1004 Meter ID characters 9 and 10 tototo --- ASCII F10 N/A
1005 Meter ID characters 11 and 12 tototo --- ASCII F10 N/A
1006 Meter ID characters 13 and 14 tototo --- ASCII F10 N/A
1007 Meter ID characters 15 and 16 tototo --- ASCII F10 N/A
1008 Meter ID characters 17 and 18 tototo --- ASCII F10 N/A
1009 Meter ID characters 19 and 20 tototo --- ASCII F10 N/A
100A Reserved
to
100F Reserved
PREFERENCES 1010 Default Message Time 1 to 1201*** 1 min x0.1 F1 10 = 1.0 min
1011 Default Message Brightness 0 to 100 20 % F1 60 %
1012 Display Filter Constant 1 to 10 1 --- F1 4
1013 Reserved
to
1017 Reserved
RS485 COM1
SERIAL PORT
1018 Serial Communication Address 1 to 255 1 --- F1 1
1019 Modbus Baud Rate for RS485 COM1 0 to 4 1 --- F12 3 = 9600
101A Parity for RS485 COM1 0 to 2 1 --- F13 0 = NONE
101B Reserved
to
101F Reserved
RS485 COM2
SERIAL PORT
1020 Modbus Baud Rate for RS485 COM2 0 to 4 1 --- F12 3 = 9600
1021 Parity for RS485 COM2 0 to 2 1 --- F13 0 = NONE
1022 Reserved
to
1027 Reserved
RS232
SERIAL PORT
1028 Modbus Baud Rate for RS232 0 to 4 1 --- F12 3 = 9600
1029 Parity for RS232 0 to 2 1 --- F13 0 = NONE
102A Reserved
to
102F Reserved
CALCU-
LATION
PARAMETERS
1030 Current Demand Calculation Type 0 to 2 1 --- F28 0 = Block Interval
1031 Current Demand Time Interval 5 to 180 1 minutes F1 30 min
1032 Power Demand Calculation Type 0 to 2 1 --- F28 0 = Block Interval
1033 Power Demand Time Interval 5 to 180 1 minutes F1 30 min
1034 Energy Cost Per kWh 1 to 50000 1 ¢ x 0.01 F1 10.00 ¢
1035 Extract Fundamental 0 to 1 1 --- F11 0=DISABLE
1036 Reserved
1037 Reserved
CLEAR DATA 1038 Clear Energy Values 0 to 1 1 --- F31 0 = NO
1039 Clear Max Demand Values 0 to 1 1 --- F31 0 = NO
103A Clear Min/Max Current Values 0 to 1 1 --- F31 0 = NO
103B Clear Min/Max Voltage Values 0 to 1 1 --- F31 0 = NO
103C Clear Min/Max Power Values 0 to 1 1 --- F31 0 = NO
Table 7–10: PQM MEMORY MAP (Sheet 27 of 40)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS and
SCALE
FORMAT FACTORY DEFAULT
Notes: * Data type depends on the Command Operation Code. ** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”. **** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Power Quality Meter Series and is the answer not in the manual?

GE Power Quality Meter Series Specifications

General IconGeneral
BrandGE
ModelPower Quality Meter Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals