7-44 PQM Power Quality Meter GE Power Management
7.3 MODBUS MEMORY MAP 7 MODBUS COMMUNICATIONS
7
ANALOG
INPUT
continued
1099 Analog In Alt Name 3
rd
and 4
th
char. --- --- ASCII F10 AL”
109A Analog In Alt Name 5
th
and 6
th
char. --- --- ASCII F10 “T ”
109B Analog In Alt Name 7
th
and 8
th
char. --- --- ASCII F10 “ A”
109C Analog In Alt Name 9
th
and 10
th
char. -- -- ASCII F10 “NA”
109D Analog In Alt Name 11
th
and 12
th
char. -- -- ASCII F10 “LO”
109E Analog In Alt Name 13
th
and 14
th
char. --- --- ASCII F10 “G
109F Analog In Alt Name 15
h
and 16
th
char. ---- ---- ASCII F10 “IN
10A0 Analog In Alt Name 17
th
and 18
th
char. --- --- ASCII F10 “PU”
10A1 Analog In Alt Name 19
th
and 20
th
char. --- --- ASCII F10 “T “
10A2 Analog In Alt Units 1
st
and 2
nd
char. --- --- ASCII F10 “ U”
10A3 Analog In Alt Units 3
rd
and 4
th
char. --- --- ASCII F10 “ni”
10A4 Analog In Alt Units 5
th
and 6
th
char. --- --- ASCII F10 “ts”
10A5 Analog In Alt Units 7
th
and 8
th
char. --- --- ASCII F10 “”
10A6 Analog In Alt Units 9
th
and 10
th
char. --- --- ASCII F10 ““
10A7 Analog Input Alt 4 mA Value 0 to 65000 1 --- F1 0
10A8 Analog Input Alt 20 mA Value 0 to 65000 1 --- F1 0
10A9 Analog Input Alt Relay 0-4 1 --- F29 0=OFF
10AA Analog Input Alt Level 0 to 65000 1 --- F1 0
10AB Analog Input Alt Delay 5 to 6000 5 0.1 xs F1 100=10.0 s
10AC Reserved
10AD Reserved
10AE Reserved
10AF Reserved
SWITCH A 10B0 Switch A Name characters 1 and 2 --- --- ASCII F10 ““
10B1 Switch A Name characters 3 and 4 --- --- ASCII F10 “ S”
10B2 Switch A Name characters 5 and 6 --- --- ASCII F10 “WI”
10B3 Switch A Name characters 7 and 8 --- --- ASCII F10 “TC”
10B4 Switch A Name characters 9 and 10 --- --- ASCII F10 “H
10B5 Switch A Name characters 11 and 12 --- --- ASCII F10 “IN“
10B6 Switch A Name characters 13 and 14 --- --- ASCII F10 “PU”
10B7 Switch A Name characters 15 and 16 --- --- ASCII F10 “T ”
10B8 Switch A Name characters 17 and 18 --- --- ASCII F10 A “
10B9 Switch A Name characters 19 and 20 --- --- ASCII F10 ““
10BA Switch A Function 0 to 14 1 --- F20 0=NOT USED
10BB Switch A Activation 0 to 1 1 --- F27 1=CLOSED
10BC Switch A Time Delay 0 to 6000 1 0.1 xs F1 0.0 s
10BD Reserved
10BE Reserved
10BF Reserved
Table 7–10: PQM MEMORY MAP (Sheet 30 of 40)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS and
SCALE
FORMAT FACTORY DEFAULT
Notes: * Data type depends on the Command Operation Code. ** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”. **** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Power Quality Meter Series and is the answer not in the manual?

GE Power Quality Meter Series Specifications

General IconGeneral
BrandGE
ModelPower Quality Meter Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals