GE Power Management PQM Power Quality Meter 4-25
4 PROGRAMMING 4.3 S2 SYSTEM SETUP
4
4.3.3 ANALOG INPUT
Figure 4–15: SETPOINTS PAGE 2 – SYSTEM SETUP / ANALOG INPUT
]] SETPOINTS
]] S2 SYSTEM SETUP
]] SETPOINTS
]] S3 OUTPUT RELAYS
SETPOINT
] CURRENT/VOLTAGE
] CONFIGURATION
] ANALOG INPUT
]
ANALOG IN MAIN/ALT
SELECT RELAY: OFF
ANALOG IN MAIN NAME:
MAIN ANALOG INPUT
Range: AUX1, AUX2, AUX3, OFF
ANALOG IN MAIN
UNITS: mA
MAIN 4mA VALUE:
0
MAIN 20mA VALUE:
0
ANALOG IN MAIN RELAY:
OFF
] ANALOG OUTPUT 4
]
ANALOG IN MAIN LEVEL:
100
ANALOG IN MAIN
DELAY: 10.0 s
ANALOG IN ALT NAME:
ALT ANALOG INPUT
ANALOG IN ALT
UNITS:
ALT 4 mA VALUE:
0
ALT 20mA VALUE:
0
ANALOG IN ALT
RELAY: OFF
ANALOG IN ALT LEVEL:
100
ANALOG IN ALT
DELAY: 10.0 s
Range: 0 to 65000; Step: 1
Range: ALARM, AUX1,
AUX2, AUX3, OFF
Range: 0 to 6500; Step: 1
Range: 0 to 65000; Step: 1
Range: 10 alphanumeric characters
Range: 20 alphanumeric characters
Range: 0.5 to 600.0 s
Step: 0.5 s
Range: 0 to 65000
Step: 1
Range: ALARM, AUX1,
AUX2, AUX3, OFF
Range: 0 to 6500
Step 1
Range: 0 to 65000
Step: 1
Range: 20 alphanumeric characters
Range: 10 alphanumeric characters
Range: 0.5 to 600.0 s
Step: 0.5 s