COMMUNICATION INTERFACE
181
Multi-Drop mode
When using the Multi-Drop mode, the entire SCPI
command list developed for the PSU can be used.
Each unit can be individually controlled after a
slave unit has been selected. For this function
check, we will assume that the master unit is
assigned to address 0, while a slave is assigned
address 5.
Run this query command via the terminal
application after the instruments have been
configured for multi-unit control with Multi-Drop
mode. See page 174.
SCPI commands
Command or response
Status
INST:SEL 0
Typing
*IDN?
Typing
GW-INSTEK,PSU150-10,,T0.01.12345678
Return
Selects the unit with address 0 and
returns its identity string.
Note
INST:SEL 5
Typing
*IDN?
Typing
GW-INSTEK, PSU150-10,,T0.01.12345678
Return
Selects the unit with address 5 and
returns its identity string.
Note
INST:SEL 6
Typing
Selects the unit with address 6 (not
configured in our example). An error is
displayed on the master front panel.
Note
INST:SEL 0
Typing
SYST:ERR?
Typing
-221, “Settings conflict”
Return
Query the system errors. “Settings
Note

Table of Contents

Other manuals for GW Instek PSU Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GW Instek PSU Series and is the answer not in the manual?

GW Instek PSU Series Specifications

General IconGeneral
BrandGW Instek
ModelPSU Series
CategoryPower Supply
LanguageEnglish

Related product manuals