The motor was stopped because the maximum
motor runtime for this gate movement was
reached (limit switch was not reached in the
maximum runtime)
[Gate check required]
The main loop counter of the motor controller
has overflowed (fatal exception error)
The variable of the state machine has reached an
invalid value (fatal exception error)
The gate did not leave the limit switch within the
maximum permissible time period (4 sec.) (gate
disengaged or very difficult to operate) [gate
check required]
One of the specified maintenance events (gate
cycles, maintenance interval) has occurred
The limit positions of the gate are undefined for
the control system software (e.g. both limit
switch contacts open)
The sought-after display text was not found in
the memory
An error occurred when writing a text into the
memory
An error occurred in relation to a pointer address
for a text in memory
The motor was stopped due to a motor
monitoring signal (return signals not plausible)
The supply voltage at the DC power module is
too low (e.g. current switched off; battery too
weak)
The DC power module has detected a short
circuit to the motor
The DC power module has detected an
excessively high operating temperature
The voltage monitoring system for the release
signal has measured an excessively high value
The voltage monitoring system for the release
signal has measured an excessively low value