7 Test run
202
SMGB0087 rev.0 - 12/2013
Operation DipSwitchSetting Operation Remarks
Manual
Defrost
Manual defrost operation starts
Press PSW1 for more than 3 se-
conds during heating operation, the
defrost operation is started after 2
minutes.This function is not availa-
ble within 5 minutes after starting
heating operation
Manual defrost operation nis-
hes
Defrost operation is automatically
ended and the heating operation is
started.
Defrost operation is available regar-
dless of frosting condition and total time
of heating operation.
Defrost operation in not performed
when the temperature of outdoor heat
exchanger is higher than 10ºC, high
pressure is higher than 3.3 MPa (33kgf/
cm
2
G) or Thermo-OFF.
• Do not repeat defrost operation fre-
quently.
N O T E
IncaseofRAS-(2-2.5)HVNPorRAS-3HVNCoperationisperformedbyDSW301onthePCBoftheoutdoorunitinstead
ofDSW1.